Bộ điều khiển Control unit SG-RS 309-2 Mayser
Ready for operation
The control unit is operated with a voltage of 24 to 36 V DC. When the supply voltage is connected, the green “P” LED is lit up.
When the sensors are not activated, the OSSDs from monitoring circuit 1 (OSSD 1.1, OSSD 1.2) and monitoring circuit 2 (OSSD 2.1, OSSD 2.2) are in the ON state. The signal outputs from monitoring circuit 1 (M1) and monitoring circuit 2 (M2) are LOW.
If sensor 2 is not connected, then all specifications for monitoring circuit 2 can be ignored.
If the control unit is being operated with only one sensor (mode: “monitoring circuit 2 inactive”), then it needs to be connected to terminals Y1 and Y2. Termi- nals Y3 and Y4 for sensor 2 remain unconfigured.
Sensor activated
If sensor 1 is activated, then the OSSDs from monitoring circuit 1 are in the OFF state, signal output M1 is HIGH. The yellow LED “S1” is lit up. If sensor 2 is acti- vated, then the OSSDs from monitoring circuit 2 are in the OFF state, signal out- put M2 is HIGH. The yellow LED “S2” is lit up. If sensor 1 and sensor 2 are activat- ed, then the OSSDs from monitoring circuit 1 and monitoring circuit 2 are in OFF state, signal outputs M1 and M2 are HIGH. The yellow LEDs “S1” and “S2” are lit up.