P2-400CH For 4-phase, operate multi-fan, control related to harmonic and power
Instrumentation
Sensor input PT-100Ω (3Wires) 4 CH (can choose out of 1CH~4CH)
Temperature measurement range - 40 ℃ ~ 250 ℃ Measurement for 200ms
Voltage and current ranges Voltage: 10 ~ 110[V], Current : 0.5 ~ 5[A] Measurement for 200ms
Precision / scale
Temperature : ±0.5 ℃(Full Scale) / 0.1 ℃
Voltage, Current : ±3 %(Full Scale) /
Voltage: 0.1 [V], Current : 0.1 [A]
Major functions
) Always display the PEAK temperature value
2) Attention and alarm functions(Alarm 1 and Alarm 2) Relay output available
3) FAN control function (AUTO and MANUAL functions),operate multi fan (determine whether fan is normal or not and indicate actuation time)
Relay output available
4) Function to decide whether SENSORS are abnormal or not Relay output available
5) Operating date and frequency of Alarm 2 can be recorded 30 times
6) Function for measurment of voltage current and harmonic, and also for VA, THD, 3~25 TH, K-FACTORY
Connection to the secondary circuit of PT and CT(Either ON or OFF in control can be selected.)
Output
Output for
attention and alarm 10A 250VAC, 10A 30VDC(Max.) Alarm 1, Alarm 2
FAN 1 Output 16A 250VAC, 16A 30VDC(Max.) FAN 1
FAN 2 Output 16A 250VAC, 16A 30VDC(Max.) FAN 2
SENSOR FAULT
Output 10A 250VAC, 10A 30VDC(Max.) either product adnormal or power off
Input
Voltage PT Secondary voltage 110[V]
Current CT Secondary current 5[A]
Communication function: RS-485 MODBUS-RTU (4800, 9600, 19200bps Possible to choose)4~20mA DC
1) Current output for the present PEAK temperature value 0 ℃ ~ 200 ℃
2) circulating current output regarding R, S, T phase (can be changeable) temperature values (Time: 9, 7, 5 second)
Product size / Panel cutting size 153(W) Ⅹ 92(H) Ⅹ 148(D)mm (136(W) Ⅹ 75(H)mm)
Control power / Power consumption AC100 ~ 240V(50/60Hz) or 100-130Vd.c. / 9W
Reliability and certification According to IEC61000-4 and IEC61010-1, CE, CB EMC, safety
Product weight 850g
Etc. The case is made of frame retarding ABS material