Symptom

Problem

Solution

The A25 is not sensing properly.

The sensing element may not be extended into the airstream or the sensing element is contacting an object inside of the duct (or plenum).

Insert the sensing element as far as possible into the airstream without allowing it to contact any object inside the duct (or plenum).

The system does not operate.

Incorrect switch connections or improper wiring.

Damaged sensor. The A25 is tripped.

Ensure that the wiring connections follow the wiring diagrams in the Wiring section.

Check connections. Replace the A25. Reset the A25.

A25 does not lockout upon a temperature rise beyond the setpoint. The A25 does not sense the correct air temperature.
A25 will not reset.

The A25 is defective. Replace the A25. The A25 is defective. page7image922548896 page7image922549376 page7image922549856page7image922550336Replace the A25.

The temperature in the duct (or plenum) Check system for overheating or fire. is not 20F° (11C°) below the setpoint.