Three-phase power analyzer (balanced and unbalanced), assembly on DIN rail, with a very compact size, and 4-quadrant measurement.
Other features include:
Consumption
3 VA
Frequency
50...60 Hz
Nominal voltage
230 Vc.a.(-15…+10%)
Size (mm) width x height x depth
53 x 85 x 85 (mm)
Envelope
Self-extinguishing V0 plastic
Fastening
DIN rail 46227
Weight (kg)
0,178
Protection class
IP 51 (Front), IP 31 (unmounted)
Relative humidity (without condensation)
5…95%
Working temperature
-10…+50 ºC
Certifications
CE, UL, VDE
Electrical safety, Maximum height (m)
2000
Electrical safety, Installation category
CAT III 300V / 520V, IEC 61010
Standards
IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 55011
Nominal current (In)
In/250 mA
Phase current measuring range
0,2%...120% (ITF)
Permanent overload
1.2 In
Maximum input current consumption
0,18 VA
Frequency measuring range
45 ... 65 Hz
Nominal voltage
300V Ph-N, 520V Ph-Ph
Maximum input voltage consumption
0,7 VA
Stop bits (ModBus)
1-2
Parity
without, even, odd
Protocol
ModBus RTU
Speed
1200-2400-4800-9600-19200
Peripheral number
0…255
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)
Pulse width
100 ms
Quantity
2
Type
NPN
Maximum frequency
5 imp / s
Maximum current
50 mA
Maximum voltage
24 Vdc
Current measurement sensors
External transformers
Voltage measurement sensors
Direct voltage
Power factor measurement
0,5…1
Phase voltage measurement
0.5% ± 1 digit