Features
• Controlling the return air in fume cupboards and controlling the supply and return air in laboratories,
clean rooms, hospital wards and operating theatres using a VAV box or a damper and flow probe
• Static measurement of differential pressure based on the capacitive method of measurement
• Zero point can be calibrated using software
• Adjustable end values of the differential pressure measuring range1)
• 50...150 Pa
• 100...300 Pa
• Can be used for measuring in areas with dirty or contaminated return air
• Brushless DC motor guarantees minimum energy consumption and a long service life
• Electromechanical torque-based switch-off for safe operation
• Extremely simple installation due to self-centring shaft adapter
• Disengageable gear unit for manual adjustment and positioning of damper
• Easy programming of the following applications using SAUTER CASE Components:2)
• Volume flow control
• Room pressure control
• Duct pressure control
• Flow control for fume cupboards
• Efficient control algorithm for fast control loops
• Integrated second control loop for:3)
• Room-pressure control: can be ideally combined with EGP 100 with symmetrical measuring
range
• Fume-cupboard control ideally combined with SVU 100, SGU 100 and FCCP 200
• 2 x RS-485 bus interface on RJ12 and connection terminal
• Up to 31 subscribers in a segment with SLC (SAUTER Local Communication) protocol
• Communication within network via BACnet MS/TP4)
• Integration of EY-RU 3** digital room operating units
• FCCP 200 display and alarm unit for fume-cupboard control or room monitoring
• Input and output signals for integrating:
• Setpoints and actual values
• Analogue output
• Priority control via switching contacts