Bộ điều khiển hòa đồng bộ và chia tải Woodward 8440-2150 LS-521 CONTROL-LS-521-5/P1

0944911836 Ms. Duyên 0972835740 Ms. Hà 0385097045 Mr. Hiếu 0392468875 Ms. Anh 0707602728 Ms. Vân
Bộ điều khiển hòa đồng bộ và chia tải Woodward 8440-2150 LS-521 CONTROL-LS-521-5/P1

Bộ điều khiển hòa đồng bộ và chia tải Woodward 8440-2150 LS-521 CONTROL-LS-521-5/P1

8440-2150

LS-521

CONTROL-LS-521-5/P1

Woodward’s LS-5 Series relays are synchronizer controllers with integrated mains decoupling and protection features. The applications range from independent synch check relay to complex power management with multiple utility feeds, bus tie-breakers and group breakers in combination with Woodward’s easYgen-3400XT/3500XT equipped genset controllers.
  • Woodward 8440-2150
  • Liên hệ
  • 1948
  • Thông tin sản phẩm
  • Bình luận

The LS-5 Series are synchronizer and load share controllers with integrated protective functions. They are designed to enable complex power management applications with multiple incoming mains and bus breakers in combination with easYgen-3400/3500 equipped genset controllers.

 

The LS-5 devices will manage synchronization, loading and unloading on each bus segment and send the required voltage and frequency references via CAN bus to the easYgen-3400/3500 genset controllers. LS-5 devices which are located on the incoming mains breakers will automatically detect mains failures and start the corresponding gensets accordingly. Wiring efforts are reduced to a minimum, since only one CAN bus connection is required between all LS-5 and easYgen-3400/3500 controllers. It is not required to wire any AC measurement signals or discrete inputs/outputs between the LS-5 and easYgen-3400/3500 controllers.

 

Extensive remote control capabilities via discrete inputs or interfaces are provided to easily integrate the LS-5 into each application environment.

The back panel mounted LS-521 has a rugged aluminum chassis for use in harsh environments or confined spaces.

 

Features include:

Up to 16 LS-5 units can be operated in one network with up to 32 easYgen-3400/3500

Phase match or slip frequency synchronization with voltage matching

Full protection package ( including df/dt (ROCOF), phase shift and mains voltage increasing protection according to new German grid code requirements in VDE-0126-1-1)

Segment control for the load sharing

Event Log with up to 300 entries

Automatic date and time synchronization between the LS-5 units and the connected easYgen-3400/3500 controls

LS-5 “Stand alone” mode without the easYgen-3400/3500 is possible

Preconfigured application modes for the most common applications in the field (MCB or MCB/GGB application)

Automatic and Manual mode

Full remote control via CAN or RS-485 interface

In case transformers are used in the application, vector group adjustment is available

Breaker open/close failure detection

Mains decoupling “Test” mode

Multilingual capability

Lock Keypad feature

Sản phẩm cùng loại