Model: 6020-3001-00
Flame Scanner
Replaces part no: G 601
Flame amplifier 3001
analog display, 2-channel, 14HP
Self checking fully electronic, once per second
Mode of operation continuous, intermittent and
72-hours-operation
Safety Integrity Level SIL 2, SIL 3 in combination with
Flame Scanner 2.0, 2.0GT, 2.0L, 2.0LA
Certificates CE, DVGW, CSA, UL, SIL 2/SIL 3
Norms EN298, IEC61508, CAN/CSA-E60730-1, CAN/CSA-C22.2
No. 60730-2-5, UL60730-2-5
Power supply 24 V DC
Current consumption
Current consumption Scanner
max. 300 mA
max. 200 mA per Flame Scanner
Ambient temperature -20 °C to +70 °C
Type of protection IP00
Cable length 500 m (1000 m with special specification)
Flame intensity 0/4 mA to 20 mA (Ra < 360 Ohm)
Flame relay two changeover contacts, potential-free
max. switching voltage 250 V ohmic load
max. switching current 1 A ohmic load
max. switching capacity 300 VA
Parameter channels two, separately adjustable, remote selection
Safety switch-OFF time adjustable (1 s to 6 s)
Sensitivity range adjustable (99 steps)
Switching point prealarm adjustable (10 steps)
Pre-alarm output 24 V DC, 100 mA