Cảm biến chênh áp Sauter EGP 100: Di€erential pressure transducer

0944911836 Ms. Duyên 0972835740 Ms. Hà 0385097045 Mr. Hiếu 0392468875 Ms. Anh 0707602728 Ms. Vân
Cảm biến chênh áp Sauter EGP 100: Di€erential pressure transducer

Cảm biến chênh áp Sauter EGP 100: Di€erential pressure transducer

EGP 100: Di€erential pressure transducer

How energy efficiency is improved

Allows precise measuring of room pressures, duct pressures or volume flows to optimise energy

consumption in ventilation systems

Areas of use

Optimised for applications such as filter monitoring, room or duct pressure monitoring, level

monitoring in fluids, actuating frequency converters for fan control and recording volume flow,

especially for room air balancing in laboratories.

Features

• Exact measurement of positive, negative and differential pressures in gases

• Optimised for applications such as filter monitoring, room or duct pressure monitoring, level

monitoring in fluids, actuating frequency converters for fan control and recording volume flow,

especially for room air balancing in laboratories

• Can be ideally combined with XAFP 100 flow probe for precise measurement of volume flow

• Static pressure sensor

• Can be fitted in any position

• Can be used for dusty air or air polluted with chemicals (not ATEX approved)

• Manufacturer’s test certificate ex works

• The measuring range can be adapted optimally to the needs of the application

• Variable zero point and filter time constant to suppress pressure surges in the system

• Display shows the actual value and the signal progression (depending on type)

• Status LED for immediate indication of operating status (depending on type)

• Measuring range can be reduced to one third (depending on type)

• Fitted to either wall or DIN rail (EN 60715)

• Cover that does not require special tools to open

  • Liên hệ
  • 958
  • Thông tin sản phẩm
  • Bình luận

Type Measuring range Display Variable characteristic/LED
Weight (kg)
EGP100F101 ±75 Pa, ±0.75 mbar − − 0.17
EGP100F102 ±75 Pa, ±0.75 mbar − • 0.18
EGP100F112 ±75 Pa, ±0.75 mbar • • 0.19
EGP100F201 ±150, 1.5 mbar − − 0.17
EGP100F202 ±150, 1.5 mbar − • 0.18
EGP100F212 ±150, 1.5 mbar • • 0.19
EGP100F301 0...150 Pa,
0...1.5 mbar
− − 0.17
EGP100F302 0...150 Pa,
0...1.5 mbar
− • 0.18
EGP100F312 0...150 Pa,
0...1.5 mbar
• • 0.19
EGP100F401 0...300 Pa,
0...3.0 mbar
− − 0.17
EGP100F402 0...300 Pa,
0...3.0 mbar
− • 0.18
EGP100F412 0...300 Pa,
0...3.0 mbar
• • 0.19
EGP100F601 0...1000 Pa,
0...10.0 mbar
− − 0.17
EGP100F602 0...1000 Pa,
0...10.0 mbar
− • 0.18
EGP100F612 0...1000 Pa,
0...10.0 mbar
• • 0.19
Accessories
Type Description
0010240300 Connection set, 6 mm, complete
XAFP100F001 Flow probe to measure the air volume in ventilation ducts
CERTIFICAT001 Manufacturer’s test certificate type M
CERTIFICAT999 Test for further device (from 2 pcs.)
0300360001 USB-RS-485 converter