Duct Temperature Sensor HE-69530NP-0 Johnson Controls
Product code number | Temperature sensor type | RH Accuracy | Output scale, set point scale, control type | Enclosure style | Logo |
---|---|---|---|---|---|
HE-69120NP-0 | Ni1000 | ±2% | Proportional, 0 V to 10 V | Duct, probe | Yes |
HE-69130NP-0 | Ni1000 | ±3% | Proportional, 0 V to 10 V | Duct, probe | Yes |
HE-69520NP-0 | Pt1000 Class A | ±2% | Proportional, 0 V to 10 V | Duct, probe | Yes |
HE-69530NP-0 | Pt1000 Class A | ±3% | Proportional, 0 V to 10 V | Duct, probe | Yes |
HE-69S30NP-0 | Silicon | ±3% | Proportional, 0 V to 10 V | Duct, probe | Yes |
Product | HE-69xx Series Duct Probe Humidity and Temperature Sensor | ||
Power requirements | 12 VDC to 30 VDC or 18 VAC to 30 VAC at 50/60 Hz, Class 2 | ||
Current draw | DC supply | 5 mA excluding load | |
AC supply | 14 mA excluding load | ||
Acceptable wire gauge | 16 AWG to 24 AWG wire; 18 AWG wire preferred | ||
Humidity element at 77°F (25°C) | Signal | 0 VDC to 5 VDC or 0 VDC to 10 VDC, 1K ohm maximum load | |
Accuracy | HE-69x2 | ±2% RH for 20% to 80% RH at 77°F (25°C) | |
±4% RH for 10% to 20% and 80% to 90% RH at 77°F (25°C) | |||
HE-69x3 | ±3% RH for 20% to 80% RH at 77°F (25°C) | ||
±5% RH for 10% to 20% and 80% to 90% RH at 77°F (25°C) |
|||
Temperature coefficient | -0.03% RH/°C | ||
Temperature sensors | Thin film nickel | Accuracy | ±0.34°F (0.18°C) at 70°F (21°C) |
Reference resistance | 1K ohm at 70°F (21°C) | ||
Resistance change | Approximately 3 ohm/°F (5 ohm/°C) | ||
Silicon | Accuracy | ±1°F (0.6°C) at 70°F (21°C) | |
Reference resistance | 1,035 ohm at 77°F (25°C) | ||
Resistance change | Approximately 4 ohm/°F (8 ohm/°C) | ||
Thin film platinum | Accuracy | ±0.65°F at 70°F (±0.36°C at 21°C) | |
Reference resistance | 1K ohm at 32°F (0°C) | ||
Resistance change | Approximately 2 ohm/°F (4 ohm/°C) | ||
Electrical connections | 3-position and 2-position screw terminal blocks | ||
Ambient operating conditions | 32°F to 140°F (0°C to 60°C) | ||
0% to 100% RH, 85°F (29.4°C) maximum dew point | |||
Survival operating conditions | -40°F to 140°F (-40°C to 60°C) | ||
0% to 100% RH, 85°F (29.4°C) maximum dew point | |||
Materials | Blue plastic cover with blue plastic housing and probe | ||
Dimensions | Duct probe (H x W x D) | 3.28 in. x 3.25 in. x 8.27 in. (83 mm x 83 mm x 210 mm) | |
Probe (L x D) | 6.25 in. x 0.98 in. (159 mm x 25 mm) | ||
Shipping weight | 0.6 lb (0.3 kg) | ||
Compliance | United States | UL Listed, CCN XAPX, File E27734; to UL 60730-1; and IEC 60730-2-13. Plenum Rated (UL 2043) | |
Canada | cUL Listed, CCN XAPX7, File E27734; to CAN/CSA E60730-1; and CAN/CSAE60730-2-13 | ||
Europe | CE Mark - Johnson Controls declares that this product is in Compliance with the essential requirements and other relevant provisions of the EMC Directive. | ||
Australia and New Zealand | RCM Mark, Australia/NZ Emissions Compliant |