Thiết bị đo mức Hitrol HT-100RS I HT-100RSH I HT-100RS-EX
Installation : Top
Ambient Temp. : -20 ~ +60℃
Fluid Temp. : Max. 80℃
Operating Pressure : Up to 20kg/cm2(300#)
Power Source : DC 24V
Output : DC 4~20mA(2-wire)
Enclosure : Ex-Proof(Ex d IIC T6,IP65)
Applications : Liquid
Length : 1,000mm
Resolution : +-10mm
As liquid level is changed in the tank, the float which is manufactured in accordance with the specific gravity of liquid moves upward or downward along the guide pipe with the same liquid level by buoyancy. The magnet is installed in the float and it activates reed switches that are installed in the guide pipe continuously, and activation of reed switches changes the resistance value. The variation of resistance value is transmitted to the R/I converter in the housing and it converts this resistance value to current output of DC 4~20mA continuously.
● Water and Wastewater facilities
● Oil, Acid , Solvent, LPG, Petrochemicals
● Drinks, Beer equipment, etc.
● Other Industries